Summary of Drinking Water Samples Tested by the Penn State Agricultural Analytical Services Laboratory

York County

8/9/2007 - 6/24/2025, 752 Samples

Test Parameter Units Number of Samples Tested Median Minimum Maximum Number of samples failing EPA Std Percent of samples failing EPA Std EPA Drink Water Std
Total
Coliform
MPN/100
mL
722 0.0 0.0 2419.6 331 45.8 0
E.
Coli
MPN/100
mL
722 0.0 0.0 200.5 58 8.0 0
pH
-
657 6.7 4.7 9.8 276 42.0 6.5-8.5
Total
Dissolved
Solids
mg/L 657 147.0 20.0 1020.0 9 1.4 500
Corrosivity
Index*

-
292 -1.9 -5.4 0.9 228 78.1 -
Hardness mg/L 317 68.4 0.8 459.7 - - -
Nitrate+Nitrite
N
mg/L 382 4.6 0.2 33.1 43 11.3 10
Chloride mg/L 56 12.9 1.5 320.0 1 1.8 250
Sulfate mg/L 60 10.1 1.0 42.4 0 0.0 250
Aluminum mg/L 21 0.0 0.0 0.1 2 9.5 0.05-0.2
Arsenic mg/L 182 0.00 0.001 0.013 1 0.5 0.01
Barium mg/L 111 0.03 0.00 0.72 0 0.0 2
Cadmium mg/L 48 0.00 0.001 0.002 0 0.0 0.005
Calcium mg/L 292 14.72 0.25 135.71 - - -
Chromium mg/L 48 0.0 0.001 0.005 0 0.0 0.1
Copper mg/L 353 0.03 0.01 7.72 3 0.8 1.0,1.3
Iron mg/L 298 0.1 0.1 25.0 27 9.1 0.3
Lead-1st
draw
mg/L 211 0.00 0.003 0.201 40 19.0 0.015
Lead-Running mg/L 260 0.003 0.003 0.844 14 5.4 0.015
Magnesium mg/L 292 5.72 0.05 45.59 - - -
Manganese mg/L 298 0.01 0.01 3.92 43 14.4 0.05
Mercury mg/L 53 0.00 0.000 0.001 0 0.0 0.002
Nickel mg/L 48 0.01 0.005 0.229 - - -
Sodium mg/L 42 16.23 0.29 133.73 - - -
Zinc mg/L 48 0.02 0.005 0.36 0 0.0 5

*For corrosivity index, failure criteria based on less than -0.5 or greater than 0.5