Summary of Drinking Water Samples Tested by the Penn State Agricultural Analytical Services Laboratory

Perry County

9/12/2007 - 6/20/2024, 487 Samples

Test Parameter Units Number of Samples Tested Median Minimum Maximum Number of samples failing EPA Std Percent of samples failing EPA Std EPA Drink Water Std
Total
Coliform
MPN/100
mL
473 0.0 0.0 200.5 215 45.5 0
E.
Coli
MPN/100
mL
473 0.0 0.0 200.5 38 8.0 0
pH
-
350 7.5 5.4 9.5 37 10.6 6.5-8.5
Total
Dissolved
Solids
mg/L 347 135.0 20.0 2100.0 7 2.0 500
Corrosivity
Index*

-
124 -0.7 -4.7 0.8 85 68.5 -
Hardness mg/L 134 71.5 0.8 613.8 - - -
Nitrate+Nitrite
N
mg/L 179 0.9 0.2 22.9 6 3.4 10
Chloride mg/L 11 2.3 1.0 28.3 0 0.0 250
Sulfate mg/L 18 11.0 1.0 235.9 0 0.0 250
Aluminum mg/L 3 0.0 0.0 0.0 0 0.0 0.05-0.2
Arsenic mg/L 82 0.00 0.001 0.039 16 19.5 0.01
Barium mg/L 38 0.05 0.00 0.52 0 0.0 2
Cadmium mg/L 26 0.00 0.001 0.002 0 0.0 0.005
Calcium mg/L 122 18.29 0.25 138.81 - - -
Chromium mg/L 26 0.0 0.003 0.005 0 0.0 0.1
Copper mg/L 151 0.01 0.01 1.95 1 0.7 1.0,1.3
Iron mg/L 128 0.1 0.1 41.3 29 22.7 0.3
Lead-1st
draw
mg/L 93 0.00 0.003 0.089 9 9.7 0.015
Lead-Running mg/L 105 0.003 0.003 0.167 6 5.7 0.015
Magnesium mg/L 122 5.57 0.05 64.88 - - -
Manganese mg/L 127 0.01 0.01 1.84 39 30.7 0.05
Mercury mg/L 25 0.00 0.001 0.001 0 0.0 0.002
Nickel mg/L 26 0.01 0.005 0.012 - - -
Sodium mg/L 8 6.82 1.42 42.30 - - -
Zinc mg/L 26 0.01 0.005 0.04 0 0.0 5

*For corrosivity index, failure criteria based on less than -0.5 or greater than 0.5